All citations for Lost Creek Rehabilitation and Nursing Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Lost Creek Rehabilitation and Nursing Center

Last standard health inspection on record

June 30, 2026

Showing 1 to 14 of 14 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of June 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 27, 2025).

  2. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of June 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 27, 2025).

  3. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of June 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 27, 2025).

  4. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of November 21, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2022).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 21, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2022).

  6. No harm, with potential for more than minimal harm

    Meet requirements for the use and maintenance of medical gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0922, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 21, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2022).

  7. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of June 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 22, 2026).

  8. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of June 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2026).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of June 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 27, 2025).

  10. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 27, 2025).

  11. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of November 21, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2022).

  12. No harm, with potential for more than minimal harm

    Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0343, Smoke Deficiencies. Inspection of November 21, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2022).

  13. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of November 21, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2022).

  14. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 21, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.