All citations for Maple Heights

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Maple Heights

Last standard health inspection on record

December 18, 2025

Showing 1 to 17 of 17 citations

  1. No harm, with potential for more than minimal harm

    Install a two-hour-resistant firewall separation.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0133, Construction Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 30, 2025).

  2. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 18, 2025).

  3. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 17, 2025).

  4. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 17, 2025).

  5. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  6. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 17, 2025).

  7. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 12, 2026).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 18, 2025).

  10. No harm, with potential for more than minimal harm

    Have restrictions on the use of highly flammable decorations.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0753, Miscellaneous Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 18, 2025).

  11. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 16, 2026).

  12. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 18, 2025).

  13. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 16, 2026).

  14. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2025).

  15. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 17, 2025).

  16. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2025).

  17. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of May 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 17, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.