All citations for Memorial Hospital of Gardena D/P SNF

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Memorial Hospital of Gardena D/P SNF

Last standard health inspection on record

April 10, 2026

Showing 1 to 16 of 16 citations

  1. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 10, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2026).

  2. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of February 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 18, 2025).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2024).

  4. No harm, with potential for more than minimal harm

    Have restrictions on the use of flammable curtains.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0751, Miscellaneous Deficiencies. Inspection of February 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2024).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2024).

  6. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of February 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 18, 2025).

  7. No harm, with potential for more than minimal harm

    Construct fire resistant interior walls.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0331, Smoke Deficiencies. Inspection of February 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2024).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 10, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 10, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2026).

  10. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 18, 2025).

  11. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of February 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2024).

  12. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2024).

  13. No harm, with potential for minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of April 10, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2026).

  14. No harm, with potential for minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of February 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 18, 2025).

  15. No harm, with potential for minimal harm

    List the names and contact information of those in the facility.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of February 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2024).

  16. No harm, with potential for minimal harm

    Provide emergency officials' contact information.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of February 9, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.