All citations for Mission Nursing Home

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Mission Nursing Home

Last standard health inspection on record

May 22, 2026

Showing 1 to 23 of 23 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  2. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of May 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  3. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  4. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 21, 2025).

  5. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2025).

  6. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 21, 2025).

  7. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 21, 2025).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2025).

  9. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2024).

  10. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2024).

  11. No harm, with potential for more than minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2024).

  12. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2024).

  13. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  14. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2025).

  15. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2025).

  16. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2025).

  17. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 28, 2024).

  18. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2024).

  19. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 21, 2025).

  20. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 21, 2025).

  21. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2024).

  22. No harm, with potential for more than minimal harm

    Ensure proper storage of liquid oxygen.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0930, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2024).

  23. No harm, with potential for minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.