All citations for Monroe Health and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Monroe Health and Rehabilitation Center

Last standard health inspection on record

February 26, 2026

Showing 1 to 14 of 14 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of February 26, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 26, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2023).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of October 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 28, 2019).

  6. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of February 26, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 27, 2026).

  7. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of February 26, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 27, 2026).

  8. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of February 26, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  9. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of February 26, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 18, 2026).

  10. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 26, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  11. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 26, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 12, 2026).

  12. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of March 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  13. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of October 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 28, 2019).

  14. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 28, 2019).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.