All citations for Monterey Palms Health Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Monterey Palms Health Care Center

Last standard health inspection on record

May 14, 2026

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    A waiver was granted (May 10, 2023).

  2. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  3. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (June 2, 2024).

  4. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of May 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (June 2, 2024).

  5. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  6. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  7. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  8. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  10. No harm, with potential for minimal harm

    Create arrangements with other facilities to receive patients.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0025, Emergency Preparedness Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  11. No harm, with potential for minimal harm

    Provide emergency officials' contact information.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  12. No harm, with potential for minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  13. No harm, with potential for minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.