All citations for Monterey Palms Health Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Monterey Palms Health Care Center

Last standard health inspection on record

May 14, 2026

Showing 1 to 25 of 30 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 14, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 5, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 14, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 4, 2026).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 14, 2025).

  4. No harm, with potential for more than minimal harm

    Properly install and monitor supervisory attachments on automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0352, Smoke Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 24, 2025).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 24, 2025).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    A waiver was granted (May 10, 2023).

  7. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 14, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 4, 2026).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 14, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 5, 2026).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 24, 2025).

  10. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  11. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of May 14, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 4, 2026).

  12. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 14, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 4, 2026).

  13. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 21, 2025).

  14. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 21, 2025).

  15. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (June 2, 2024).

  16. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of May 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (June 2, 2024).

  17. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  18. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  19. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  20. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  21. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 10, 2023).

  22. No harm, with potential for minimal harm

    Establish staff and initial training requirements.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 21, 2025).

  23. No harm, with potential for minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 24, 2025).

  24. No harm, with potential for minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 24, 2025).

  25. No harm, with potential for minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of January 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 24, 2025).