All citations for Nevada State Veterans Home - Boulder City

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Nevada State Veterans Home - Boulder City

Last standard health inspection on record

February 13, 2026

Showing 1 to 24 of 24 citations

  1. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  3. No harm, with potential for more than minimal harm

    Ensure medical gas and vacuum systems have documented maintenance programs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0907, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2026).

  4. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  6. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2026).

  7. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  8. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  9. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  10. No harm, with potential for more than minimal harm

    Establish policies and procedures including evacuation.

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0020, Emergency Preparedness Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  11. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  12. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  13. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  14. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 8, 2026).

  15. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 8, 2026).

  16. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of December 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 21, 2025).

  17. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of December 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 21, 2025).

  18. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of December 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 21, 2025).

  19. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of December 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 21, 2025).

  20. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of medical gas and medical vacuum systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0902, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 21, 2025).

  21. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  22. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  23. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  24. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 30, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).