All citations for Northampton Manor Nursing and Rehabilitation Cente

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Northampton Manor Nursing and Rehabilitation Cente

Last standard health inspection on record

January 30, 2026

Showing 1 to 18 of 18 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  4. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 11, 2024).

  5. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 11, 2024).

  6. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 11, 2024).

  7. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 11, 2024).

  8. No harm, with potential for more than minimal harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0916, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 11, 2024).

  9. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  10. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  11. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  12. No harm, with potential for more than minimal harm

    Construct fire resistant interior walls.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0331, Smoke Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  13. No harm, with potential for more than minimal harm

    Have proper openings in smoke barrier doors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0379, Smoke Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  14. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  15. No harm, with potential for more than minimal harm

    Have restrictions on the use of highly flammable decorations.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0753, Miscellaneous Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  16. No harm, with potential for more than minimal harm

    Have restrictions on the use of portable space heaters.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0781, Miscellaneous Deficiencies. Inspection of January 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2026).

  17. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    A waiver was granted (January 8, 2025).

  18. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 11, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.