All citations for Olympia Transitional Care and Rehabilitation

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Olympia Transitional Care and Rehabilitation

Last standard health inspection on record

April 24, 2026

Showing 1 to 18 of 18 citations

  1. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 21, 2026).

  2. No harm, with potential for more than minimal harm

    Conduct risk assessment and an All-Hazards approach.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0006, Emergency Preparedness Deficiencies. Inspection of April 1, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  3. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of April 1, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  4. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of April 1, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  5. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 1, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  6. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  7. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  9. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  10. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of April 1, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  11. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 21, 2026).

  12. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 21, 2026).

  13. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 21, 2026).

  14. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 1, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  15. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  16. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  17. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  18. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.