All citations for Oxford Health and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Oxford Health and Rehabilitation Center

Last standard health inspection on record

November 21, 2025

Showing 1 to 19 of 19 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of July 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 31, 2024).

  2. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of July 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 28, 2024).

  3. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2023).

  4. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2023).

  5. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2023).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of November 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  7. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of November 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  8. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of November 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of November 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 30, 2026).

  11. No harm, with potential for more than minimal harm

    Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0111, Construction Deficiencies. Inspection of July 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 28, 2024).

  12. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0200, Egress Deficiencies. Inspection of July 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 28, 2024).

  13. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of July 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 28, 2024).

  14. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of July 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 28, 2024).

  15. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2023).

  16. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2023).

  17. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2023).

  18. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2023).

  19. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.