All citations for Park Regency Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Park Regency Care Center

Last standard health inspection on record

December 12, 2025

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of December 12, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 29, 2025).

  2. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  3. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  4. No harm, with potential for more than minimal harm

    Have properly installed hallway dispensers for alcohol-based hand rub.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0325, Smoke Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  6. No harm, with potential for more than minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  7. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  9. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  11. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 11, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2022).

  12. No harm, with potential for minimal harm

    Provide emergency officials' contact information.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of October 10, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 16, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.