All citations for Park View Care Center
State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.
Last standard health inspection on record
March 5, 2026
Showing 1 to 15 of 15 citations
No harm, with potential for more than minimal harm
Meet requirements for sections of health care facilities separated by fire resistive construction.
The home gave a date the problem would be corrected (April 24, 2026).
No harm, with potential for more than minimal harm
Have restrictions on the use of highly flammable decorations.
The home gave a date the problem would be corrected (April 24, 2026).
No harm, with potential for more than minimal harm
Have generator or other power source capable of supplying service within 10 seconds.
The home gave a date the problem would be corrected (April 24, 2026).
No harm, with potential for more than minimal harm
Use approved construction type or materials.
The home gave a date the problem would be corrected (June 23, 2023).
No harm, with potential for more than minimal harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
The home gave a date the problem would be corrected (June 23, 2023).
No harm, with potential for more than minimal harm
Provide properly protected cooking facilities.
The home gave a date the problem would be corrected (June 23, 2023).
No harm, with potential for more than minimal harm
Provide a written emergency evacuation plan.
The home gave a date the problem would be corrected (June 23, 2023).
No harm, with potential for more than minimal harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
The home gave a date the problem would be corrected (June 23, 2023).
No harm, with potential for more than minimal harm
Ensure proper usage of power strips and extension cords.
The home gave a date the problem would be corrected (June 23, 2023).
No harm, with potential for more than minimal harm
Ensure that testing and maintenance of electrical equipment is performed.
The home gave a date the problem would be corrected (June 23, 2023).
No harm, with potential for more than minimal harm
Install corridor and hallway doors that block smoke.
The home gave a date the problem would be corrected (June 23, 2023).
No harm, with potential for more than minimal harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
The home gave a date the problem would be corrected (January 20, 2020).
No harm, with potential for more than minimal harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
The home gave a date the problem would be corrected (January 20, 2020).
No harm, with potential for more than minimal harm
Install an approved automatic sprinkler system.
The home gave a date the problem would be corrected (January 20, 2020).
No harm, with potential for more than minimal harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
The home gave a date the problem would be corrected (January 20, 2020).
Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.