All citations for Parkhill North Nursing Home

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Parkhill North Nursing Home

Last standard health inspection on record

December 18, 2025

Showing 1 to 24 of 24 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2023).

  2. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2023).

  3. No harm, with potential for more than minimal harm

    Develop Emergency Preparedness policies and procedures.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0013, Emergency Preparedness Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  4. No harm, with potential for more than minimal harm

    Provide emergency officials' contact information.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  5. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  6. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  7. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 5, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2024).

  9. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of June 5, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2024).

  10. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home has a plan to correct it (July 21, 2023).

  11. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2023).

  12. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2023).

  13. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2023).

  14. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2023).

  15. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2023).

  16. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  17. No harm, with potential for more than minimal harm

    Meet other general requirements that are deficient.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0300, Egress Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  18. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  19. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0521, Services Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  20. No harm, with potential for more than minimal harm

    Have an externally vented heating system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0522, Services Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  21. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

  22. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 5, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2024).

  23. No harm, with potential for minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of April 24, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2023).

  24. No harm, with potential for minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of September 16, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2019).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.