All citations for Parsons Hill Rehabilitation & Health Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Parsons Hill Rehabilitation & Health Care Center

Last standard health inspection on record

April 29, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 20, 2026).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 20, 2026).

  3. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 20, 2026).

  4. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 20, 2026).

  5. No harm, with potential for more than minimal harm

    Install a two-hour-resistant firewall separation.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0133, Construction Deficiencies. Inspection of March 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2025).

  6. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of March 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2025).

  7. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2025).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of March 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2025).

  9. No harm, with potential for more than minimal harm

    Have horizontal exits used in accordance with safety requirements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0226, Egress Deficiencies. Inspection of January 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 9, 2024).

  10. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2025).

  11. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2025).

  12. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2025).