All citations for Pearl at the Tillers
State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.
Last standard health inspection on record
March 6, 2025
Showing 1 to 23 of 23 citations
No harm, with potential for more than minimal harm
Install a fire alarm system that can be heard throughout the facility.
The home gave a date the problem would be corrected (March 24, 2025).
No harm, with potential for more than minimal harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
The home gave a date the problem would be corrected (March 24, 2025).
No harm, with potential for more than minimal harm
Establish staff and initial training requirements.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
Conduct testing and exercise requirements.
The home gave a date the problem would be corrected (February 26, 2024).
No harm, with potential for more than minimal harm
Install emergency lighting that can last at least 1 1/2 hours.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
Have approved installation, maintenance and testing program for fire alarm systems.
The home gave a date the problem would be corrected (February 28, 2024).
No harm, with potential for more than minimal harm
Inspect, test, and maintain automatic sprinkler systems.
The home gave a date the problem would be corrected (March 8, 2024).
No harm, with potential for more than minimal harm
Have simulated fire drills held at unexpected times.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
The home gave a date the problem would be corrected (February 29, 2024).
No harm, with potential for more than minimal harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
Have generator or other power source capable of supplying service within 10 seconds.
The home gave a date the problem would be corrected (March 15, 2024).
No harm, with potential for more than minimal harm
Have approved installation, maintenance and testing program for fire alarm systems.
The home gave a date the problem would be corrected (January 30, 2023).
No harm, with potential for more than minimal harm
Inspect, test, and maintain automatic sprinkler systems.
A waiver was granted (April 1, 2023).
No harm, with potential for more than minimal harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
The home gave a date the problem would be corrected (January 31, 2023).
No harm, with potential for more than minimal harm
Have generator or other power source capable of supplying service within 10 seconds.
The home gave a date the problem would be corrected (January 31, 2023).
No harm, with potential for more than minimal harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
The home gave a date the problem would be corrected (March 24, 2025).
No harm, with potential for more than minimal harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
Provide properly protected cooking facilities.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
Install an approved automatic sprinkler system.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
Ensure proper usage of power strips and extension cords.
The home gave a date the problem would be corrected (February 23, 2024).
No harm, with potential for more than minimal harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
The home gave a date the problem would be corrected (January 20, 2023).
No harm, with potential for more than minimal harm
Ensure proper usage of power strips and extension cords.
The home gave a date the problem would be corrected (February 3, 2023).
Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.