All citations for Preferred Care at Old Bridge, LLC

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Preferred Care at Old Bridge, LLC

Last standard health inspection on record

March 31, 2025

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  2. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  3. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  4. No harm, with potential for more than minimal harm

    Properly install and monitor supervisory attachments on automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0352, Smoke Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  5. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  7. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2023).

  8. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2023).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  10. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  11. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  12. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 31, 2023).

  13. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.