All citations for Roscoe Gardens Skilled Nursing and Rehab

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Roscoe Gardens Skilled Nursing and Rehab

Last standard health inspection on record

December 30, 2025

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of December 30, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 16, 2026).

  2. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of December 30, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 16, 2026).

  3. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of December 30, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 16, 2026).

  4. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of October 10, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 13, 2024).

  5. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of July 27, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 15, 2023).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of July 27, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 15, 2023).

  7. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of July 27, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 15, 2023).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of July 27, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 15, 2023).

  9. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of July 27, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 15, 2023).

  10. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 30, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 16, 2026).

  11. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of October 10, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 13, 2024).

  12. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of October 10, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 13, 2024).

  13. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of October 10, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 13, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.