All citations for Rushville Nursing & Rehab Ctr

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Rushville Nursing & Rehab Ctr

Last standard health inspection on record

June 30, 2026

Showing 1 to 21 of 21 citations

  1. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  3. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  4. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 25, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2023).

  7. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of May 25, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2023).

  8. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 25, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2023).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 25, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2023).

  10. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of April 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  11. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of April 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  12. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  13. No harm, with potential for more than minimal harm

    Have restrictions on the use of portable space heaters.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0781, Miscellaneous Deficiencies. Inspection of April 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  14. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 9, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  15. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  16. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  17. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  18. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  19. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of June 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  20. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 25, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 21, 2023).

  21. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of May 25, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.