All citations for Russell Park Rehabilitation & Living Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Russell Park Rehabilitation & Living Center

Last standard health inspection on record

May 21, 2025

Showing 1 to 20 of 20 citations

  1. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 24, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 27, 2023).

  2. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2024).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 24, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 27, 2023).

  4. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2025).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2025).

  6. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2025).

  7. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2025).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2025).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2024).

  10. No harm, with potential for more than minimal harm

    Have proper openings in smoke barrier doors.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0379, Smoke Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2024).

  11. No harm, with potential for more than minimal harm

    Have restrictions on the use of flammable curtains.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0751, Miscellaneous Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2024).

  12. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of October 24, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 27, 2023).

  13. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of October 24, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 27, 2023).

  14. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of October 24, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 27, 2023).

  15. No harm, with potential for more than minimal harm

    Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0361, Smoke Deficiencies. Inspection of October 24, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 27, 2023).

  16. No harm, with potential for more than minimal harm

    Meet other general requirements that are deficient.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0500, Services Deficiencies. Inspection of October 24, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 27, 2023).

  17. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 24, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 27, 2023).

  18. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 30, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 8, 2022).

  19. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of June 30, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 8, 2022).

  20. No harm, with potential for minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.