All citations for Saint Elizabeth Home East Greenwich

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Saint Elizabeth Home East Greenwich

Last standard health inspection on record

April 23, 2026

Showing 1 to 8 of 8 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 23, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 23, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 23, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 23, 2026).

  3. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  4. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  6. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  7. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  8. No harm, with potential for minimal harm

    Establish policies and procedures including evacuation.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0020, Emergency Preparedness Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.