All citations for Sainte Anne Extended Healthcare

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Sainte Anne Extended Healthcare

Last standard health inspection on record

May 21, 2026

Showing 1 to 25 of 29 citations

  1. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2026).

  2. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2026).

  3. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2026).

  4. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2026).

  5. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2026).

  6. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0541, Services Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 11, 2026).

  7. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 15, 2026).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2026).

  9. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2025).

  10. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2025).

  11. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2025).

  12. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2025).

  13. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0541, Services Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    A waiver was granted.

  14. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2025).

  15. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2025).

  16. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2025).

  17. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2025).

  18. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of December 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 17, 2024).

  19. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of December 14, 2023. Found during a standard inspection.

    A waiver was granted.

  20. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of December 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 17, 2024).

  21. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0541, Services Deficiencies. Inspection of December 14, 2023. Found during a standard inspection.

    A waiver was granted.

  22. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of December 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 17, 2024).

  23. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 17, 2024).

  24. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2026).

  25. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 15, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.