All citations for Sam Swope Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Sam Swope Care Center

Last standard health inspection on record

February 12, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0916, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 16, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 12, 2024).

  3. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 12, 2024).

  4. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 16, 2026).

  5. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0541, Services Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 16, 2026).

  6. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 16, 2026).

  7. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 12, 2024).

  8. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 12, 2024).

  9. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 12, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 12, 2024).

  11. No harm, with potential for more than minimal harm

    Have proper fire barriers, ventilation and signs for the transfilling of oxygen.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0927, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 12, 2024).

  12. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 16, 2026).