All citations for Silver Tree Nursing and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Silver Tree Nursing and Rehabilitation Center

Last standard health inspection on record

June 12, 2026

Showing 1 to 16 of 16 citations

  1. No harm, with potential for more than minimal harm

    Establish policies and procedures including evacuation.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0020, Emergency Preparedness Deficiencies. Inspection of June 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 17, 2026).

  2. No harm, with potential for more than minimal harm

    Establish staff and initial training requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of June 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2026).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 10, 2026).

  4. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  5. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of April 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  7. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of June 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 13, 2026).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 17, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 17, 2026).

  10. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of June 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 13, 2026).

  11. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  12. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of April 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  13. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of April 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  14. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  15. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 7, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2024).

  16. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 17, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.