All citations for Southampton Rehabilitation and Healthcare Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Southampton Rehabilitation and Healthcare Center

Last standard health inspection on record

September 3, 2021

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 17 of 17 citations

  1. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    A waiver was granted (December 14, 2018).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  3. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  4. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    A waiver was granted (December 14, 2018).

  5. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of September 3, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 12, 2021).

  6. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of September 3, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 12, 2021).

  7. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of September 3, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 12, 2021).

  8. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  9. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  10. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  11. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    A waiver was granted (February 22, 2019).

  12. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  13. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    A waiver was granted (February 22, 2019).

  14. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  15. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  16. No harm, with potential for minimal harm

    Meet other general requirements that are deficient.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0300, Egress Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

  17. No harm, with potential for minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 4, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 14, 2018).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.