All citations for St Paul Elder Services, Inc

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to St Paul Elder Services, Inc

Last standard health inspection on record

May 12, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 2, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  2. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of March 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2024).

  3. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of March 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2024).

  4. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2024).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2024).

  6. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of April 2, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  7. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 2, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  8. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of April 2, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

  9. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of March 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2024).

  11. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of March 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2024).

  12. No harm, with potential for minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 2, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 25, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.