All citations for St. Theresa Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to St. Theresa Care Center

Last standard health inspection on record

June 14, 2025

Showing 1 to 21 of 21 citations

  1. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of June 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2025).

  2. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of June 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2025).

  3. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2025).

  4. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 19, 2023).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 19, 2023).

  6. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0541, Services Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 19, 2023).

  7. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 19, 2023).

  8. No harm, with potential for more than minimal harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0916, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 19, 2023).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 19, 2023).

  10. No harm, with potential for more than minimal harm

    Meet requirements for sections of health care facilities separated by fire resistive construction.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0131, Construction Deficiencies. Inspection of January 9, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  11. No harm, with potential for more than minimal harm

    Have an alternate power supply for its alarm system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0344, Smoke Deficiencies. Inspection of January 9, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  12. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 9, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  13. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of January 9, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  14. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of January 9, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  15. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 9, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  16. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of June 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2025).

  17. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of June 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2025).

  18. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2025).

  19. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 19, 2023).

  20. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of January 9, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  21. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 9, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.