All citations for Stonebridge Chillicothe

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Stonebridge Chillicothe

Last standard health inspection on record

April 24, 2026

Showing 1 to 18 of 18 citations

  1. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 30, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 12, 2025).

  3. No harm, with potential for more than minimal harm

    Have horizontal exits used in accordance with safety requirements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0226, Egress Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  4. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  5. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  6. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  7. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  9. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 30, 2026).

  10. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 30, 2026).

  11. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 30, 2026).

  12. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 30, 2026).

  13. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  14. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  15. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  16. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of June 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  17. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 12, 2025).

  18. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 12, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.