All citations for Taconic Rehabilitation And Nursing At Hopewell

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Taconic Rehabilitation And Nursing At Hopewell

Last standard health inspection on record

February 12, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of May 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2023).

  2. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2023).

  3. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of July 5, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 30, 2019).

  4. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of July 5, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 30, 2019).

  5. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of May 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2023).

  6. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of July 5, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 30, 2019).

  7. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of July 5, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 30, 2019).

  8. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0541, Services Deficiencies. Inspection of July 5, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 30, 2019).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 5, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 30, 2019).

  10. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 5, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 30, 2019).

  11. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 5, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 30, 2019).

  12. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.