All citations for Tekakwitha Living Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Tekakwitha Living Center

Last standard health inspection on record

January 22, 2026

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 8, 2026).

  2. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of July 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2024).

  3. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2026).

  4. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 8, 2026).

  5. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of July 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2024).

  6. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2023).

  7. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 1, 2023).

  8. No harm, with potential for minimal harm

    Install resident room doors of proper design and width.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0233, Egress Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    No follow-up visit needed (January 22, 2026).

  9. No harm, with potential for minimal harm

    Conform to length requirements for dead end corridors.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0251, Egress Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    No follow-up visit needed (January 22, 2026).

  10. No harm, with potential for minimal harm

    Install resident room doors of proper design and width.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0233, Egress Deficiencies. Inspection of July 18, 2024. Found during a standard inspection.

    Fire Safety Evaluation Survey (August 15, 2024).

  11. No harm, with potential for minimal harm

    Conform to length requirements for dead end corridors.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0251, Egress Deficiencies. Inspection of July 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 15, 2024).

  12. No harm, with potential for minimal harm

    Install resident room doors of proper design and width.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0233, Egress Deficiencies. Inspection of June 1, 2023. Found during a standard inspection.

    Fire Safety Evaluation Survey (June 1, 2023).

  13. No harm, with potential for minimal harm

    Conform to length requirements for dead end corridors.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0251, Egress Deficiencies. Inspection of June 1, 2023. Found during a standard inspection.

    Fire Safety Evaluation Survey (June 1, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.