All citations for The Grove Post-Acute Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to The Grove Post-Acute Care Center

Last standard health inspection on record

December 4, 2025

Showing 1 to 20 of 20 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of December 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2025).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of December 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 24, 2025).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 24, 2025).

  4. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 10, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 5, 2024).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of December 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2025).

  6. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of December 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2025).

  7. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2025).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of December 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 24, 2025).

  9. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of December 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2025).

  10. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of December 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2025).

  11. No harm, with potential for more than minimal harm

    Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0926, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 19, 2025).

  12. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of December 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 24, 2025).

  13. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of December 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 24, 2025).

  14. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of December 10, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 5, 2024).

  15. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 10, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 5, 2024).

  16. No harm, with potential for minimal harm

    List the names and contact information of those in the facility.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of December 10, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 5, 2024).

  17. No harm, with potential for minimal harm

    Establish staff and initial training requirements.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of December 10, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 5, 2024).

  18. No harm, with potential for minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of December 10, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 5, 2024).

  19. No harm, with potential for minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of December 10, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 5, 2024).

  20. No harm, with potential for minimal harm

    Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0343, Smoke Deficiencies. Inspection of December 10, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 5, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.