All citations for Twinbrook Healthcare and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Twinbrook Healthcare and Rehabilitation Center

Last standard health inspection on record

April 16, 2026

Showing 1 to 16 of 16 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 16, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 16, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 14, 2024).

  4. No harm, with potential for more than minimal harm

    Install a two-hour-resistant firewall separation.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0133, Construction Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 9, 2025).

  5. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 9, 2025).

  6. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 14, 2024).

  7. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 16, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  8. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 16, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  9. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 14, 2024).

  10. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 14, 2024).

  11. No harm, with potential for minimal harm

    Meet other general requirements.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 14, 2024).

  12. No harm, with potential for minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level B.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 16, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  13. No harm, with potential for minimal harm

    Have power receptacles that are properly grounded.

    Pattern (more than a few residents). CMS level B.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 16, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  14. No harm, with potential for minimal harm

    Use approved construction type or materials.

    Pattern (more than a few residents). CMS level B.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 9, 2025).

  15. No harm, with potential for minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level B.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 9, 2025).

  16. No harm, with potential for minimal harm

    Have power receptacles that are properly grounded.

    Pattern (more than a few residents). CMS level B.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 9, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.