All citations for Vienna Nursing And Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Vienna Nursing And Rehabilitation Center

Last standard health inspection on record

February 20, 2026

Showing 1 to 23 of 23 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  2. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  3. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2024).

  4. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2024).

  5. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 14, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 27, 2022).

  7. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  8. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  9. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  10. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  11. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  12. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  13. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2024).

  14. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2024).

  15. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2024).

  16. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2024).

  17. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of October 14, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 27, 2022).

  18. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of October 14, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 27, 2022).

  19. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of October 14, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 27, 2022).

  20. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 14, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 27, 2022).

  21. No harm, with potential for minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  22. No harm, with potential for minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  23. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 20, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.