All citations for Waters of Chesterfield Skilled Nursing Facility

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Waters of Chesterfield Skilled Nursing Facility

Last standard health inspection on record

March 30, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of March 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 1, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 30, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 1, 2026).

  3. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of October 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (December 16, 2024).

  4. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (December 16, 2024).

  5. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of January 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 14, 2024).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 14, 2024).

  7. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of January 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 14, 2024).

  8. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of January 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2025).

  9. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of January 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2025).

  10. No harm, with potential for more than minimal harm

    Have proper fire barriers, ventilation and signs for the transfilling of oxygen.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0927, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2025).

  11. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of January 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 14, 2024).

  12. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of January 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 14, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.